On this page
The standard was published in the Diario Oficial de la Federación on 11 March 2022 and replaced NOM-001-SEMARNAT-1996. It is not a change of values: it is a change of parameters. A plant sized from the old table can fall short while appearing to comply.
What it covers, and what it does not
It sets the permissible limits for pollutants in wastewater discharged to receiving bodies owned by the nation, and it is mandatory for the parties responsible for those discharges. Enforcement sits with the Secretariat through the Commission and the Prosecutor, each within its own remit.
Two cases are excluded: discharges from drains intended exclusively for stormwater, and discharges made directly to municipal drainage and sewerage systems. The latter are governed by NOM-002-SEMARNAT-1996 and, where they exist, by the conditions set by the operating utility.
The receiving-body categories
The standard does not give one limit: it gives a table per receiving-body type and, within each, separates the monthly average (P.M.), the daily average (P.D.) and the instantaneous value (V.I.). The same effluent can comply in a river and fail for infiltration, because the values are not the same.
- Rivers, streams, canals and drains.
- Reservoirs, lakes and lagoons.
- Mexican marine zones.
- Soil.
- Irrigation of green areas.
- Infiltration and other irrigation, including karst ground.
Where the authority issues particular discharge conditions — through a classification declaration for the national water body or in the discharge permit — those parameters and limits prevail over the general table. Before sizing, check whether the site already has particular conditions.
The limits that decide the design
These are the monthly-average values for four of the six categories. Nutrients and the microbiological indicator are what change most between categories, and they are what make the treatment train more expensive.
Wide table: scroll sideways to see every column.
| Parameter (mg/L unless stated) | Rivers, streams, canals, drains | Reservoirs, lakes, lagoons | Mexican marine zones | Infiltration and other irrigation |
|---|---|---|---|---|
| Total suspended solids | 60 | 20 | 20 | 20 |
| COD | 150 | 100 | 85 | 60 |
| Total organic carbon | 38 | 25 | 21 | 15 |
| Total nitrogen | 25 | 15 | 25 | 15 |
| Total phosphorus | 15 | 5 | 15 | 5 |
| Fats and oils | 15 | 15 | 15 | 15 |
| Escherichia coli (MPN/100 ml) | 250 | 250 | 250 | 50 |
| pH (pH units) | 6–9 | 6–9 | 6–9 | 6–9 |
Monthly average (P.M.). The standard also sets a daily average and an instantaneous value for each parameter, and separate columns for soil, irrigation of green areas and karst ground. The text published in the DOF is the reference.
Two laboratory rules change the report: COD is analysed and reported where chloride is below 1000 mg/L, and total organic carbon where it is at or above that. For the microbiological indicator, below 3500 µS/cm of electrical conductivity Escherichia coli is reported, and above it faecal enterococci.
Acute toxicity is set at 2 toxicity units at 15 minutes of exposure, and true colour at spectral absorption coefficients of 7.0 m⁻¹ at 436 nm, 5.0 m⁻¹ at 525 nm and 3.0 m⁻¹ at 620 nm. Metals and cyanide sit in Table 2; for a discharge to a river the monthly average is 0.2 mg/L arsenic, 0.2 cadmium, 1 cyanide, 4 copper and 1 chromium.
What changed from the 1996 standard
- Organic matter is expressed as COD and total organic carbon. The current standard sets no BOD₅ limit.
- True colour and acute toxicity are added, and they enter into force after the rest of the table.
- The microbiological indicator depends on conductivity: Escherichia coli or faecal enterococci.
- Discharges to municipal sewerage are expressly outside the scope of this standard.
When each block applies
- Published in the DOF: 11 March 2022.
- General entry into force: 365 calendar days after publication, on 11 March 2023.
- Tables 1 and 2 and the normative appendix: 3 April 2023.
- True colour and acute toxicity: in the fourth year after publication, on 11 March 2026.
- Until each block applied, discharges remained subject to NOM-001-SEMARNAT-1996.
The standard provided for guidance for regulated parties to submit compliance programmes, and that guidance was published in the DOF on 5 December 2022. A programme does not change the limit: it changes the deadline for reaching it, and it has to be filed in time.
What it means for the treatment train
The receiving-body table fixes three decisions. First, how much nitrogen and phosphorus has to come out: the difference between 15 and 5 mg/L of total phosphorus decides whether chemical or biological phosphorus removal is needed. Second, whether the microbiological indicator requires disinfection. Third, whether the effluent needs a polishing step — filtration or carbon — to reach the COD or total organic carbon limit.
A discharge to a river usually calls for secondary treatment with nitrification and denitrification, phosphorus removal and disinfection. A discharge to infiltration is stricter on solids, nutrients and the microbiological indicator, and usually requires filtration after the biological stage before the water is infiltrated.
The most common error is sizing to the 1996 standard out of habit. The COD and nutrient values do not match, and the plant falls short on exactly the parameters the current standard tightened.
What we need to size the plant
- The receiving body and its classification, or the discharge permit with its particular conditions.
- Design flow and the discharge pattern.
- Influent characterisation: COD, TSS, total nitrogen, total phosphorus, fats and oils, pH and conductivity.
- Chloride, to know whether the laboratory reports COD or total organic carbon.
- Whether reuse is intended, and for what duty.
- Site data: footprint, access for delivery, and the power supply (V / Hz / phase).
Questions we answer on Mexican projects
Does it apply to a discharge to the municipal sewer? No. NOM-001-SEMARNAT-2021 expressly excludes discharges to municipal drainage and sewerage systems; those fall under NOM-002-SEMARNAT-1996 and the conditions set by the operating utility.
Why is there no BOD₅? Because the current standard sets organic matter as COD and total organic carbon. If a project still specifies BOD₅, it is worth checking which limit it is actually being sized against.
When do colour and acute toxicity apply? In the fourth year after publication, on 11 March 2026.
And the metals? They are in Table 2, with limits by receiving-body type and by monthly average, daily average and instantaneous value; the text published in the DOF is the reference.