Thailand building effluent standards 2024: the ก, ข, ค and ง classes

Thailand’s 2024 building effluent rules divide buildings into four classes and set ten parameters. Reading the standards notice without the designation notice gives the wrong answer about which buildings are actually controlled.

A clear glass sampling bottle on the concrete edge of an inlet channel
Operations & compliance
On this page

Two ministerial notices published in the Royal Gazette on the same day govern effluent from buildings in Thailand. The standards notice sets the limits and divides buildings into four classes. The designation notice decides which buildings are pollution sources subject to that control. A project that reads only the first will know the numbers but not whether they apply.

The two notices and when they apply

The standards notice (ประกาศกระทรวงทรัพยากรธรรมชาติและสิ่งแวดล้อม เรื่อง กำหนดมาตรฐานควบคุมการระบายน้ำทิ้งจากอาคารบางประเภทและบางขนาด พ.ศ. 2567) and the designation notice were both published on 27 August 2024, in the Royal Gazette volume 141, special part 233 ง. Both took effect the day after publication, on 28 August 2024. The standards notice repealed the 2005 standards notice; the designation notice repealed the 2005 designation, its 2011 amendment and the 2021 notice on class ค buildings.

What counts as one building

The standards notice defines a building as a structure, or a group of buildings standing on the same plot of land, whether or not the buildings are connected by drains and whether there is one outfall pipe or several. A campus with a classroom block, a canteen and two dormitories on one plot is therefore assessed as a group, and the size that decides its class is the total of those buildings, not the largest single block. This definition is where most campus projects go wrong: the class is read from the plot, not from the building that happens to be under discussion.

Three types, four classes

Buildings are divided into three types — residential, commercial and medical — and each type is banded into classes ก, ข, ค and ง by a size measure that belongs to the type: floor area for schools, offices, markets and restaurants; rooms for apartments, hotels and dormitories; beds for hospitals. The table below reproduces the bands from the standards notice.

Wide table: scroll sideways to see every column.

BuildingMeasured inกขคง
ApartmentUnits≥500100–<500<100—
DormitoryRooms—≥25050–<250<50
HotelRooms≥20060–<200<60—
School or universitym²≥25,0005,000–<25,000—<5,000
Office buildingm²≥55,00010,000–<55,0005,000–<10,000<5,000
Shopping centre or department storem²≥25,0005,000–<25,000—<5,000
Marketm²≥2,5001,500–<2,5001,000–<1,500<1,000
Restaurant or food shopm²≥2,500500–<2,500250–<500<250
Service establishment (bath, massage, sauna)m²—≥5,0001,000–<5,000<1,000
Hospital with inpatient bedsBeds≥3010–<30—<10
Daycare, elderly care, construction-worker housing————All sizes

Class bands from Article 4 of the 2024 standards notice. A dash means the notice does not place that building in that class.

The designation notice lists the buildings that are pollution sources subject to effluent control, and its definition of a building covers classes ก, ข and ค. Class ง appears in the standards table but is not among the classes the designation notice lists, so a small building in class ง should be checked with the local authority rather than assumed either to be controlled or to be exempt.

The limits, class by class

Article 5 sets ten parameters. Six are numeric limits for the four classes; the last three apply to medical buildings only. A dash means the notice sets no limit for that class.

Wide table: scroll sideways to see every column.

Parameterกขคง
pH5.5–9.05.5–9.05.5–9.05.5–9.0
BOD (mg/L)≤20≤30≤40Residential ≤50; commercial and medical ≤100
Suspended solids (mg/L)≤30≤40≤50≤60
Total dissolved solids (mg/L)≤1,000≤1,000≤1,300—
Sulfide (mg/L)≤1.0≤1.0≤1.0—
TKN (mg/L)≤35≤35≤40—
Oil and grease (mg/L)≤20≤20≤20Residential ≤20; commercial and medical ≤50
Total coliform (MPN/100 mL)≤5,000 (medical only)≤5,000 (medical only)——
Fecal coliform (MPN/100 mL)≤1,000 (medical only)≤1,000 (medical only)——
Free chlorine (mg/L)≤1.0 (medical only)≤1.0 (medical only)——

Article 5 of the 2024 standards notice. The medical-building TDS limit is not an absolute value; see below.

The one limit that is not an absolute value

For residential and commercial buildings the TDS limit is an absolute figure: 1,000 mg/L in classes ก and ข, and 1,300 mg/L in class ค. For a medical building in class ก or ข the notice sets the limit as an increase — no more than 1,000 mg/L above the total dissolved solids of the normal supply water. Copying “TDS 1,000” from the residential column onto a hospital therefore checks a different quantity from the one the notice defines, and the plant has to be designed against the supply water at the site.

What the notice does not regulate

COD is not in the table, and neither are total phosphorus, ammonia nitrogen, temperature or colour. A process guarantee written against this notice cannot promise COD removal against a COD limit the notice does not set. Factories sit outside the notice: process wastewater from an industrial plant follows the industrial effluent standard, which does set COD, and the two instruments must not be mixed. A building notice table cannot be used to check a factory outfall, and an industrial table cannot be used for a campus.

How the standards are checked

Article 6 fixes the test method for each parameter: pH by meter with a resolution of at least 0.1; BOD by the five-day 20 °C method with azide modification, or by membrane electrode or optical probe; suspended solids on a glass-fibre filter dried at 103–105 °C for at least one hour; total dissolved solids on a glass-fibre filter dried at 180 °C for at least one hour; sulfide by the iodometric or methylene blue method; TKN by Kjeldahl; oil and grease by solvent extraction and weighing; coliform by multiple-tube fermentation; free chlorine by titration, iodometric electrode or a colorimetric method. Article 8 points to the standard methods of the Environmental Engineering Association of Thailand or the latest APHA/AWWA/WEF edition.

Where the sample is taken

Article 9 requires the sample to be taken where the effluent is discharged to a public water source or to the environment, or at another point that represents the effluent leaving the building; where there are several outfalls, every outfall is sampled. The method is grab sampling, not a composite. That matters for design: a plant that meets a limit on a daily average can still fail a grab sample, so equalization and disinfection have to be sized for the short-term condition, not the daily mean.

What we need before sizing a Thai building plant

  • The building type and the size measure the notice uses for it — m², rooms or beds — and whether the site is one building or a group on the same plot.
  • The class that follows from that, and any condition the local authority has added.
  • Design flow, and the daily and weekly pattern of use.
  • Influent BOD, COD, TSS, TDS, oil and grease and pH, with canteen, laboratory or process streams analysed separately.
  • The discharge point: a public water source, the environment or a treatment system.
  • Whether the site reuses treated water, and for what.
  • Power supply (V / Hz / phase), site access and lifting capacity.

Questions we answer on Thai building projects

Is the class the same as the old Type A to E? No. The 2005 notice used Type A to E. That notice was repealed, and the 2024 notice uses ก, ข, ค and ง. A specification that still asks for Type A is referring to a withdrawn scheme.

Does a small dormitory have to treat its sewage? A dormitory under 50 rooms falls in class ง. The designation notice lists classes ก, ข and ค as controlled pollution sources, so class ง sits outside that list; whether the building still needs a system depends on the local authority and on where the effluent goes. Ask before assuming either way.

We have a hospital. Which limits change? The medical columns add total coliform at 5,000 MPN/100 mL, fecal coliform at 1,000 MPN/100 mL and free chlorine at 1.0 mg/L, and they express the TDS limit as an increase over the supply water rather than an absolute value. Everything else follows the class.

Can we meet the limits by diluting? No. The designation notice prohibits dilution, and it prohibits discharging without treatment that meets the standards.

Do we need COD compliance for a campus? Not under this notice, because it sets no COD limit. A factory on the same estate is a different case and follows the industrial standard.

Tell us what the site has to treat.